Technology | True Online |
Capacity (VA/W) | 2000 / 1600 |
Input Parameters | |
Frequency Range | 40Hz ~ 70 Hz |
Phase | Single phase with ground |
Power Factor | ≥ 0.99 @ 220 to 230 VAC (input voltage) |
Voltage Range | |
Low Line Transfer | 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) |
Low Line Comeback | 175 VAC ± 5 % |
High Line Transfer | 300 VAC ± 5 % |
High Line Comeback | 290 VAC ± 5 % |
Output Parameters | |
Output Voltage | 208/220/230/240VAC |
AC Voltage Regulation | ± 3% (Batt. Mode) |
Frequency Range | 47 to 53 Hz or 57 to 63 Hz (Synchronized Range) |
Frequency Range (Batt. Mode) | 50 Hz ± 0.25Hz |
Overload | 100% to 110%: audible warning 110% to 130%: UPS shuts down in 30 seconds at battery mode or transfers to bypass mode when the utility is normal. >130%: UPS shuts down immediately at battery mode or transfer to bypass mode when the utility is normal. |
Current Crest Ratio | 3:1 |
Harmonic Distortion | ≤ 3 % THD (Linear Load) ≤ 6 % THD (Non-linear Load) |
Waveform (Batt. Mode) | Pure Sinewave |
Efficiency | |
AC Mode | ~ 88% |
Battery Mode | ~ 83% |
Transfer Time | |
AC Mode to Batt. Mode | Zero |
Inverter to Bypass | 4 ms (Typical) |
Battery Charger (Standard Model) | |
Battery Type | 12 V / 7 AH |
Numbers | 6 |
Charging Current | 4.0 A or 8.0 A(max.) |
Charging Voltage | 41.0 VDC ± 1% |
Physical Parameters | |
Dimension, D X W X H | 318 x 190 x 421 |
Net Weight (kgs) | 26 |
Emvironmental Parameters | |
Operation Humidity | 20 to 90 % RH @ 0 to 40°C (non-condensing) |
Noise Level | Less than 55dBA @ 1 Meter |
Management | 4.0 A or 8.0 A(max.) |
Smart RS-232 or USB | Supports Windows 98/2000/2003/XP/Vista/2008/ 7, Linux, and MAC |
Optional SNMP | Power management from SNMP manager and web browser |