Output
-
Output power capacity10.0 KWatts / 10.0 kVA
-
Max Configurable Power (Watts)10.0 KWatts / 10.0 kVA
-
Nominal Output Voltage230V
-
Output Voltage DistortionLess than 2%
-
Output Frequency (sync to mains)50/60Hz +/- 3 Hz
-
Other Output Voltages220, 240
-
Load Crest Factor3 : 1
-
TopologyDouble Conversion Online
-
Waveform typeSine wave
-
Output Connections(6) IEC 320 C13 (Battery Backup)(4) IEC 320 C19 (Battery Backup)(1) Hard Wire 3-wire (H N + G) (Battery Backup)(3) IEC Jumpers (Battery Backup)
-
BypassInternal Bypass (Automatic and Manual)
Input
-
Nominal Input Voltage230V , 400V 3PH
-
Input frequency40 - 70 Hz (auto sensing)
-
Input ConnectionsHard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH + N + G)
-
Input voltage range for main operations160 - 275V
-
Input voltage adjustable range for mains operation100 - 275 (half load), 173 - 476 (half load)V
-
Other Input Voltages220, 240, 380, 415
Batteries & Runtime
-
Battery typeMaintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
-
Typical recharge time1.5hour(s)
-
Replacement BatteryAPCRBC140
-
Expected Battery Life (years)3 - 5
-
RBC Quantity2
-
Extendable Run Time1
-
Extended Run OptionsAPC-Smart-UPS-SRT-10000VA-230V
-
Runtime
-
Efficiency
Communications & Management
-
Interface Port(s)RJ-45 10/100 Base-T , RJ-45 Serial , Smart-Slot , USB
-
Control panelMulti-function LCD status and control console
-
Audible AlarmAudible and visible alarms prioritized by severity
-
Emergency Power Off (EPO)Yes
-
Available SmartSlot™ Interface Quantity